Permit Number: T19CM08036
Parcel: 133132030

Address:
7666 E HELEN ST

Review Status: Active

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T19CM08036
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2020 ALEXANDRA HINES ZONING REVIEW Reqs Change 1. provide sit/plot plan
2. conform to setbacks or obtain approved DDO modification process.

Alexandra Hines
02/18/2020 ALEXANDRA HINES ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Alexandra Hines, AICP - Lead Planner

PROJECT:
T19CM08036 - 7666 E HELEN ST - Attached PATIO

TRANSMITTAL: 2/18/2020
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of ten (10) feet, or three-fourths (3/4) the height of the structure's wall facing each exterior property line (Table 6.3-2.A).

The proposed setback is four feet six inches (4' 6") based on wall height of seven feet two inches (7' 2"). The required setback is ten (10) feet.

A DDO approval is required for zoning to approve the building permit.
10/30/2019 IMONSHI1 ENGINEERING REVIEW Passed
10/30/2019 IMONSHI1 NPPO REVIEW Passed
10/30/2019 ANY BUILDING-RESIDENTIAL REVIEW Active