Permit Number: T19CM07899
Parcel: 128030070

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM07899
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2019 ERIC NEWCOMB ADA REVIEW Passed
10/25/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide structural calculations and details for the construction of the water heater support.
2. Limit the distance from the lavatory to the hot water source per table C404.5.1. IECC 2018.
10/25/2019 ROBERT SHERRY WATER REVIEW Completed
10/25/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/25/2019 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/25/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/25/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed