Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM07854
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/14/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/14/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Using the maximum allowable pipe length method (Section C404.5.1, IECC 2018), the maximum distance from the hot water source to the hot water termination for the public lavatories is 2-feet for a ½" branch. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.] |
| 01/14/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | My mistake, room OP-16 is missing a return grille, not OP-17. [Initial comment: Provide a return grille for OP-17 to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2018.] |
| 12/30/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved |