Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2020 MARTIN BROWN FIRE REVIEW Approved
01/14/2020 ROBERT SHERRY WATER REVIEW Completed
01/14/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Using the maximum allowable pipe length method (Section C404.5.1, IECC 2018), the maximum distance from the hot water source to the hot water termination for the public lavatories is 2-feet for a ½" branch. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]
01/14/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change My mistake, room OP-16 is missing a return grille, not OP-17. [Initial comment: Provide a return grille for OP-17 to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2018.]
12/30/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved