Permit Number: T19CM07841
Parcel: 12103074A

Address:
5801 E PIMA ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM07841
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2020 MARTIN BROWN FIRE REVIEW Approved
03/19/2020 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
03/19/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide a completed Special Inspections Form for required Epoxy and Expansion anchors noted in Structural Notes on sheet S1. IBC107.2.1.
2. Structural Calculations specifies a Simpson STHD 10 holdown at shearwall , but the shearwall and holdown(s) are not illustrated on plan .Please indicate the shear wall on plan and location of holdown(s) . IBC107.2.1.
03/27/2020 ROBERT SHERRY WATER REVIEW Reqs Change 1. Based on the existing plumbing fixtures visible in the drawings and the new plumbing fixtures, the estimated water demand will be 27.6 GPM. The existing 5/8" water meter is only capable of passing 20 GPM.
2. The water pressure for this address has a range of 77-84 PSI. Provide a water pressure regulator conforming to ASSE 1003 or CSA B356 to limit the water pressure to 80 PSI or less. Reference: Section 604.8, IPC 2018.
03/27/2020 STEVE SHIELDS ZONING REVIEW Passed
03/27/2020 SSHIELD1 ENGINEERING REVIEW Passed
03/31/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the intension for the water heater. On the mechanical/plumbing plan, the existing water heater is to remain but in the plumbing notes, a new 50-gallon water heater is to be installed.
2. The minimum air gap for the termination of a temperature and pressure relief valve is two pipe diameters (1-1/2" in this case). Reference: Section 504.6 (10), IPC 2018.
03/31/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Demonstrate energy code compliance for the addition to the building envelope using calculations based on the current code. Reference: Sections C103.2, C303, and C502.1, International Energy Conservation Code 2018
04/08/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved