Permit Number: T19CM07753
Parcel: 11505032D

Address:
15 W GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM07753
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2019 SBORZAK1 ZONING REVIEW Needs Review PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: Speedway Training Center - 15 W. Grant Road
T19CM07753
Building Plan (1st Review)

TRANSMITTAL DATE: October 28, 2019

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. It appears that there have been changes to the site that are not reflected on the last approved site plan, i.e. additional vehicle parking added along the front of the main building, one (1) being an additional accessible vehicle parking space that does not meet the requirements of ICC A117.1-2009 Section 501, no access aisle is provided. A new development package will need to be submitted and approved prior to approval of this building plan.

3. Until the building plan is approved by all other review agencies Zoning cannot approve the plan.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
11/06/2019 MARTIN BROWN FIRE REVIEW Approved
11/26/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change Provide the Code Analysis for the minimum number of required plumbing fixtures . IBC Chap. 29 , (P) Table 2902.1.
11/26/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces as part of this change of use. Reference: Section 403.3, IMC 2018.
3. Provide general room exhaust for any cooking appliance (e.g. hot dog roller grill, convection oven, etc.) that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2 and 507.3, IMC 2018.
11/26/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. The training room is an A3 assembly occupancy. Revise the plumbing fixture calculation including the correct occupancy types.
3. Appliances (e.g. beverage dispensers, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. At a minimum, coffee machines and non-carbonated beverage dispensers require the use of a backflow preventer listed to either ASSE 1022, ASSE 1024, or an air gap. Reference: Sections 608.1, 608.3 and 608.17.1.2, IPC 2018.
11/27/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments. Also provide a written response.
#1. Provide electrical plans sealed by an electrical registrant registered in the State of Arizona.
#2. Provide a complete electrical line diagram and load calcs for panel 'MDP'.
#3. Provide a complete electrical lighting plan.
Ref; City of Tucson Commercial Plan Submittal Requirements. www.tucsonaz.gov/pdsd
12/09/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T19CM07753

1) A development package submittal is required. Refer to coning comments
2) Once the development package and any outstanding commercial reviews have been completed Engineering can approve the building plans