Permit Number: T19CM07736
Parcel: 131120320

Address:
6008 E 30TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM07736
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2020 MROSS2 FIRE REVIEW Reqs Change Per section 503.1.1 of the 2018 International Fire Code, a fire department access road shall be within 150' of a new building. A residential fire sprinkler system would be allowed as a substitute for access. Sprinklers can be supplied by the domestic water in this situation, but a 3/4" meter would be required.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/17/2020 VFLORES1 APPROVAL SHELF Completed
10/17/2020 VFLORES1 OUT TO CUSTOMER Completed
10/17/2020 VFLORES1 REJECT SHELF Completed