Permit Number: T19CM07729
Parcel: 14029043A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM07729
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/02/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The hot water recirculation system (The recirculation loop is considered to be the source of hot water - Section 607.2, IPC 2018.) does not appear to have a recirculation pump and the hot water loop returns to the hot water pipe at the water heater. Reroute the hot water return for the recirculating hot water system to connect to the cold water inlet of the water heater. Reference: Section 607.2.2, IPC 2018. [Initial comment: The hot water connections of the restroom lavatories as shown on detail A/P-3 do not appear to be within 2'-0" of the hot water recirculation loop. The line weights used on the domestic water plan make the water piping illegible.] [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]
01/10/2020 KROBLES1 ZONING REVIEW Needs Review