Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM07729
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2020 | PMARTIN1 | ZONING | REVIEW | Needs Review | |
| 12/20/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The transfer air for the restrooms and the prep area is to be outside air that has been introduced into the areas from which the air will be transferred (i.e. 525 CFM + 300 CFM is not equal to 525 CFM). Reference: Section 403.2.2, IMC 2018. [Initial comment: Revise the ventilation calculations to include ventilation for the prep area. Reference: Sections 401.2 and 401.3, IMC 2018.] |
| 12/20/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The hot water connections of the restroom lavatories as shown on detail A/P-3 do not appear to be within 2'-0" of the hot water recirculation loop. The line weights used on the domestic water plan make the water piping illegible. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.] 2. Detail 1/P-2 shows a 2-compartment sink, not a 3-compartment sink. [Initial comment: Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.1, IPC 2018.] |