12/20/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The transfer air for the restrooms and the prep area is to be outside air that has been introduced into the areas from which the air will be transferred (i.e. 525 CFM + 300 CFM is not equal to 525 CFM). Reference: Section 403.2.2, IMC 2018. [Initial comment: Revise the ventilation calculations to include ventilation for the prep area. Reference: Sections 401.2 and 401.3, IMC 2018.]
12/20/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The hot water connections of the restroom lavatories as shown on detail A/P-3 do not appear to be within 2'-0" of the hot water recirculation loop. The line weights used on the domestic water plan make the water piping illegible. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]
2. Detail 1/P-2 shows a 2-compartment sink, not a 3-compartment sink. [Initial comment: Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.1, IPC 2018.]