Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T19CM07729
Parcel: 14029043A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM07729
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/20/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/20/2019 PMARTIN1 ZONING REVIEW Needs Review
12/20/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The transfer air for the restrooms and the prep area is to be outside air that has been introduced into the areas from which the air will be transferred. Reference: Section 403.2.2, IMC 2018. [Initial comment: Revise the ventilation calculations to include ventilation for the prep area. Reference: Sections 401.2 and 401.3, IMC 2018.]