Permit Number - T19CM07686
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2019 MALLORY RESS ZONING REVIEW Approved
10/18/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide a list of the hazardous chemicals (including the quantities being stored and in use).
2. Verify that the storage/Drying room does not require exhaust.
10/18/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/18/2019 MRESS1 ENGINEERING REVIEW Passed
10/18/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
10/18/2019 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide the water meter size and serial number
2. Show the size and location of the backflow preventer.
10/18/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a sealed plan
10/18/2019 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/28/2019 MARTIN BROWN FIRE REVIEW Approved