Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T19CM07651
Parcel: 117141430

Address:
450 S MEYER AV

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T19CM07651
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed