Permit Number: T19CM07617
Parcel: 12708187F

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM07617
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E3 and E4. Please provide a minimum text size or font of 3/32 of an inch per the City of Tucson Commercial Plan Submittal Requirements. The wording is to small to read legibly.
Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.