Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM07617
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/16/2019 | NICHOLAS ROSS | ZONING | REVIEW | Approved | |
| 10/16/2019 | RMCCOY1 | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 10/16/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Designate branch circuits and panels for the lighting and power. 2. Provide full compliance with the 2018 IECC for the lighting. 3. Provide a complete panel schedule(s). Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements. |
| 10/16/2019 | NROSS1 | ENGINEERING | REVIEW | Passed | |
| 10/16/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/16/2019 | RMCCOY1 | WATER | REVIEW | Passed | |
| 10/16/2019 | RMCCOY1 | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/16/2019 | MROSS2 | FIRE | REVIEW | Approved | |
| 10/16/2019 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |