Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM07587
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/22/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/31/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet TS1 , Project Code Review : Occupant Loads - the occupant load factor is incorrect , Amend with the correct occupant load factor. IBC Table 1004.5. 2. Sheet TS1 , Project Code Review : Total Occupants - provide the correct number of occupants . IBC Table 1004.5. 3. Sheet TS1 , Project Code Review : provide the minimum number of required plumbing fixtures . IBC Chapter 29, [P]Table 2902.1. Respond to plan review comments in writting . |
| 11/12/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 11/12/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide structural calculations and details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2018. 2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018. |
| 11/13/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 11/14/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; lighting Plan. Revise the lighting branch circuit homeruns to indicate the correct panel designations. 2. Indicate the conduit and conductor sizes and types for the 30 KVA transformer secondary feeder. Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal requirements. |