Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T19CM07563
Parcel: 99999999T

Address:
5508 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM07563
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

The revised lumen calculations still require a special inspection per section 106.2.1 (over 100,000 lumens per acre) Also revise the special inspection note to satisfy section 104.2.2.

Also per the first plan review comment, please clarify the ‘FIXTURE NOTE’ #1, plan sheet E0.1. And ‘GENERAL NOTE’ #3, plan sheet E2.0. These notes do not seem to correlate with the ‘NEW’ and ‘OLD INVENTORY’ . For example, what happens with the 30 can lights and others? They don’t seem to be accounted for in the ‘LUMEN INVENTORY’. Why are they not shown on the site lighting plan?

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC),

City of Tucson Commercial Plan Submittal Requirements