Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM07563
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/09/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. The following errors were found in the Outdoor Lighting Calculations. (a) Ref; plan sheet E0.1, E3.1. The option '1’ is for mostly Low Pressure Sodium (LPS) type lighting... The lighting utilized for exterior lighting on the project is LED type luminaires. Please revise the calculations to correlate with LED type. Should be area ‘E3’ Option 2, table 401.1. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements |