Permit Number: T19CM07563
Parcel: 99999999T

Address:
5508 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM07563
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. There was not enough information in the resubmitted plan set to verify full compliance to the Tucson/Pima County Outdoor Lighting Code. Please review the following and resubmit.
2. Provide lighting plans with the following information on the plans;
(a) Provide a complete luminaire schedule.
(a) See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing.
(b) 402.1 (light source color temperature requirements), shielding requirements, etc .
(c) Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1.
(d) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.
(e) Specify any exceptions used.
(f) Curfew lighting controls If applicable.
Do not confuse the Outdoor Lighting Code with the IECC.

Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
Dan.santacruz2tucsonaz.gov