Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM07524
Parcel: 10712170F

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T19CM07524
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2019 MARTIN BROWN FIRE REVIEW Approved
11/06/2019 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Needs Review
11/06/2019 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/06/2019 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Completed
11/06/2019 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Needs Review T19CM07524 - PLAN REVIEW COMMENTS
Reviewer: Chris Anderson, November 4, 2019
BUILDING - COMMERCIAL
1. Please respond to all comments in writing.
2. No dimension between buildings is given on the site plan, sheet 3 of 10. However, by takeoff form digital plans, it is 17'-9". Per 2018 IBC 503.1.2 and fire separation distance definition in Section 202, an imaginary line can be drawn between the buildings giving a fire separation distance of 8'-9 ½" for each building. And per 705.2.3 combustible projections (porch roof structures) extending within 5-feet from the imaginary line shall be minimum 1-hour fire-resistance-rated unless the porch areas are protected by sprinklers. By takeoff the porch roof structures extend to within 4'-6" of the imaginary line. In the plans, either provide 1-hour fire-resistance-rating for the porch roof structures between buildings or extend the sprinkler system to these areas. Ref. 2018 IBC 705.2.3.1(exception 3).
3. On sheet A1.1 under Architectural Specifications at the end of Section 01100 a note states "SEE PROJECT MANUAL FOR FULL SPECIFICATIONS." Submit the Project Manual.
4. Revise the GLASS NOTE under the window schedules on sheet A5.0 to delete "and have "U" values that meet or exceed the requirements of the 2018 I.E.C.C. (0.40 for U values and 0.25 for SHGC)." The windows shall have U-0.38 and SHGC-0.23 per the LIHTC Energy Analysis Summary on sheet A1.1 or have your energy rater rerun his program using U 0.40 and SHGC 0.25 to see if the building still complies with the 2018 IECC with those changes.
5. On sheet A7.1 please continue the Type C drywall on the demising walls in each detail to the bottom of the roof sheathing per 2018 IBC 708.4(1) unless it is intended that the roof/ceiling assembly be fire-resistance rated, in which case indicate the UL Design number for the fire-rated roof/ceiling assembly.
6. Submit special inspections certificate(s) required by the City of Tucson.
PLUMBING - COMMERCIAL
1. The Water Calculations on sheet P2.1 state that there will be a new 1 ½" water meter; however the civil Utilities + Easements Plan, sheet 5 of 10, shows both buildings tied together with a single 2" water meter. Please coordinate with Civil Engineer so that documents show the same thing.
ELECTRICAL - COMMERCIAL
1. The engineer's seal is unreadable.
11/08/2019 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: NEW MULTI-FAMILY APARTMENT BUILDING
Building plans (1st Review) 2940 N ORACLE RD
T19CM07524 - C-2 Zoning - Related to DP19-0250

TRANSMITTAL DATE: November 08, 2019


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: COMMENT: Zoning has done a review of the building plans. In addition, while the building are consistent as it relates to the zoning review purview zoning cannot approve the building plans until the Commercial Plans reviewer(s) have approved the building plans.

02. COMMENT: Zoning will review the building plans on the next submittal to assure consistency with the DP. Once the DP is approved by all reviewers and the building plans are approved by the Commercial Plans reviewers zoning can approve the building plans




If you have any questions about this transmittal, Contact Paul Camarena any time during the week at (520) 837-4082 or by email Paul.Camarena@Tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
11/27/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change 1) DP19-0250 needs to be approved prior to approval of the building plans
2) Ensure all commercial reviews are complete
3) Make sure all roof drains scupper under sidewalks/pedestrian areas as applicable
11/27/2019 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
12/02/2019 PMARTIN1 WATER REVIEW Approved