Permit Number - T19CM07414
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2020 RMCCOY1 WATER REVIEW Passed
01/02/2020 RMCCOY1 PLUMBING-COMMERCIAL REVIEW Reqs Change Sheet SP - 901 , under Gas states - Gas Note : Contractor shall include in bid 30ft. of gas line from provided gas meter to pool heater. Provide the gas line location , size , length , BTUs of heater , etc. on plans . IBC 107.2.1.
01/02/2020 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change Electrical Plan Sheet states -- Preliminary Not For Construction -- submit plans stamped , signed , and dated by an Arizona Registrant . IBC 107.2.1.
12/30/2019 STEVE SHIELDS ZONING REVIEW Approved FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM07414 - New Pool, Splash Pad and Equipment Room (Recreation Center)
Building Plan Review (2nd Review) Saguaro Trails Community Park Center Pool and Splash Pad
9925 E Drexel Road / PAD 30 Zoning

TRANSMITTAL DATE: December 11, 2019

DUE DATE: December 30, 2019

1. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers, the plans can be approved by zoning.

If you have any questions about this transmittal, Contact David Rivera on Tuesday, Wednesday or Thursday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
12/30/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 4; Sheet SP-301; Section 2: Per the 2018 International Swimming Pool and Spa Code, Section 411.2.1, The pool stairs must have a tread depth dimension not less than 24", and 411.2.3, The vertical distance from the pool coping , deck , or step surface to the upper most tread shall be not greater than 12 inches . Detail 13/SP-503 does not indicate dimensions that meet those criteria. Please verify.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/21/2020 PMARTIN1 REJECT SHELF Completed