Permit Number: T19CM07414
Parcel: 141020220

Address:
9925 E DREXEL RD

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T19CM07414
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2019 MASHFOR1 FIRE REVIEW Approved
10/25/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM07414 - New Pool, Splash Pad and Equipment Room (Recreation Center)
Building Plan Review (1st Review) Saguaro Trails Community Park Center Pool and Splash Pad
9925 E Drexel Road / PAD 30 Zoning

TRANSMITTAL DATE: October 25, 2019

DUE DATE: November 6, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the Pool, Splash Pad and equipment room plans for compliance with the approved development package. While the plans for the Pool, Splash Pad and equipment room are consistent with the approved DP as it relates to the zoning review purview the PDSD Commercial Plans reviewers must approve the plans before approval by zoning.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the plans to ensure consistency with the DP.

3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the plans can be approved by zoning.


If you have any questions about this transmittal, Contact David Rivera on Tuesday, Wednesday or Thursday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
10/25/2019 KROBLES1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet SP-001; Aquatic Feature Data: The Occupancy Load should be provided here, or reference the sheet that has that information.
2. Sheet SP-001; Code Compliance: Please add the 2018 Edition of the International Swimming Pool and Spa Code to this sheet.
3. Sheet SP-301; Sections 1, 3, and 4: A note indicates a minimum reinforcing design for the pool wall and floor. Please provide a reference to Sheet SP-701 for the deferred submittal of the pool and splash pad calculations and drawings.
4. Sheet SP-301; Section 2: Per the International Swimming Pool and Spa Code Section 411.2, pool stair treads shall not be less than 24" at the leading edge. Please verify these stairs meet that requirement.
5. Sheet SP-501; Section 1: A note indicates a minimum reinforcing design for the pool wall and floor. Please provide a reference to Sheet SP-701 for the deferred submittal of the pool and splash pad calculations and drawings.
6. Sheet SP-701; Part 1 (Swimming Pool and Splash Pad): Per this sheet, deferred submittals of the stamped and sealed engineered drawings and calculations for the pool and splash pad will follow the requirements of the IBC Sectioin 107.3.4.1. Please verify.
7. Sheet SP-701; Part 2 (Surge Tank): Please verify that stamped and sealed engineered drawings and calculations for the surge tank will be provided and will follow the requirements of the IBC Section 107.3.4.1.
8. Sheet A1.1; Occupant Load Table: In Room #113 (Warming Kitchen), please revise the number of occupants.
9. Sheet A1.1; Egress Floor Plan: The exit access travel distances are not measured per the IBC Section 1017.3. Please revise.
10. Sheet A1.1; Travel Distance: The Table indicates the maximum travel distance is 68'-6". Please indicate that distance on the building plan.
11. Sheet A1.2; Pool Enclosure Keynotes: Note 9 indicates a new steel shade canopy. This item will require stamped and sealed engineered drawings and calculations and will fololow the requirements of the IBC Section 107.3.4.1.
12. Sheet A1.2; Keynotes: Note 9 references architectural/structural plans for a steel shade canopy. There are no structural plans. Please revise the note.
13. Sheet A1.2; Pool Plan: Note 6 (Pool Equipment Enclosure) has a Section 9/S2.0 cut through that wall. There is no Sheet S2.0. Provide structural calculations and drawings for the wall and foundation.
14. Sheet A1.4; Section 4: Note 1 references the floor plan for shower enclosure walls. Provide structural calculations and drawings for the wall and foundation (Section references 11/S2.0 for the foundation).
15. Sheet A1.4; Section 1: Keynotes 1, 3, 4, 7, and 13: Please provide the thickness of the steel members.
16. General: Please provide the Special Inspection Certificate with Parts A and B completed. This can be found at www.tucsonaz.gov/PDSD.
17. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
11/04/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Show the location, size, and material of the water service piping. Reference: Section 107.2.1, IBC 2018.
2. Show the location of the natural gas meter and the size and route of the natural gas service to the pool heater.
3. Show how tepid water is to be supplied to the eyewash installation. Reference: Sections 411.1 and 411.3, IPC 2018.
11/04/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change How will the pool heater be vented. Reference; Section 107.2.1, IBC 2018.
11/04/2019 ROBERT SHERRY WATER REVIEW Reqs Change Show the location of the water meter and the associated backflow preventer.
11/05/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide plans sealed by an Electrical Engineer registered in the State of Arizona.
2. Provide complete electrical plans. See the City of Tucson Commercial Plan Submittal Requirements. www.tucsonaz.gov/pdsd.
Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal requirements. 2012 Tucson/Pima County Outdoor Lighting Code
11/07/2019 LOREN MAKUS ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2019 SBORZAK1 REJECT SHELF Completed
11/08/2019 SBORZAK1 OUT TO CUSTOMER Completed