Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM07406
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/16/2019 | MROSS2 | FIRE | REVIEW | Approved | |
10/30/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/06/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
11/06/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a metering or automatic faucet for the lavatory (L7), dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet will operate for a minimum time of 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Verify that the distance from the hot water source to the hot water termination for the public lavatory (L7), complies with the requirements of Section C404.5, IECC 2018. 3. Provide an approved vacuum relief valve (not a vacuum breaker as noted in detail L/P03.01) for the scheduled bottom-fed water heater that is located above the fixture outlets. Reference: Section 504.2, IPC 2018. |
11/06/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/06/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |