Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM07404
Parcel: 11520005K

Address:
1905 W GRANT RD

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T19CM07404
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show how the new fryer hood complies with Section 507.2.6, IMC 2018 for clearances.
2. Provide ventilation calculations.
3. Show compliance with Section 501.4, IMC 2018 for pressure equalization.
10/22/2019 MARTIN BROWN FIRE REVIEW Approved