Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T19CM07404
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/22/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/22/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Show how the new fryer hood complies with Section 507.2.6, IMC 2018 for clearances. 2. Provide ventilation calculations. 3. Show compliance with Section 501.4, IMC 2018 for pressure equalization. |