Permit Number: T19CM07373
Parcel: 107020090

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM07373
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/26/2020 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: 3224 N Freeway Industrial loop NEW SHELL BUILDING
Building plans (2nd Review) 3224 N FREEWAY INDUSTRIAL LP
T19CM07373 / T19CM07377- I-1 Zoning - Related to DP19-0246

TRANSMITTAL DATE: February 26, 2020
Due Date March 5, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: Zoning has done a review of the building plans and T.I., while the building are consistent as it relates to the zoning review purview zoning cannot approve the building plans until the Commercial Plans reviewer(s) have approved the building plans and the DP 19-0246 is approved. (As of this review the DP has yet to be approved.)

02. COMMENT: Zoning will review the building plans on the next submittal to assure consistency with the approved DP. (Once the DP is approved by all reviewers and the building plans are approved by the Commercial Plans reviewers zoning can approve the building plans.)

03. COMMENT: Assure that the site plan in the building plans package matches the site plan from the DP package.

If you have any questions about this transmittal, Contact David Rivera at (520) 837-4957 or by email David.Rivera@Tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
03/02/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide a Special Inspection Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD.
03/05/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan recommends. Also provide a written response.
1. As requested per the previous electrical plan review comment. The reviewer could not locate a written response in this resubmittal.
2. Please address comment # 4.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
03/13/2020 PMARTIN1 ENGINEERING REVIEW Needs Review