Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM07352
Parcel: 123020860

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM07352
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2019 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: II Sons
Building plans (2nd Review) 2500 E Grant Rd
T19CM07352 - C-2 Zoning - Related to DP18-0195

TRANSMITTAL DATE: November 26, 2019

DUE DATE: December 18, 2019


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: Zoning has done a review of the building plans. In addition, while the building plans are consistent, as it relates to the zoning review purview zoning cannot approve the building plans until the Commercial Plans reviewer(s) have approved the building plans.


02. COMMENT: Remove all clouds and deltas



If you have any questions about this transmittal, Contact Paul Camarena any time during the week at (520) 837-4082 or by email Paul.Camarena@Tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
11/29/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/06/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/09/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/09/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. [Initial comment: Provide third-party listing and material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2018.]
2. Table C404.5.1, IECC 2018 limits the maximum pipe length of a public lavatory from its hot water source to no more than two feet for a ½" supply. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018.]
12/09/2019 SBORZAK1 ENGINEERING REVIEW Completed