Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM07352
Parcel: 123020860

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM07352
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2019 MASHFOR1 FIRE REVIEW Approved
10/16/2019 KROBLES1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet a0.1; Project Data: The occupancy indicates Group M-Mercantile. Per the IBC Section 304, a barber shop falls under the Business Group B. Please revise.
2. Sheet a0.1; Project Data: Please revise the occupancy load for a Group B Occupancy Classification.
3. Sheet a0.1; Project Data: Since the Group B Occupancy Classification will have less than 25 total occupants, the IBC Section 2902.2(4) allows for a single unisex restroom. Please indicate this on the Restroom Calculation.
4. Sheet a0.1; Project Data: Per the IBC Table 2902.1 (Footnote e), a service sink is not required for a Group B Occupancy Classification with 15 occupants or less. Please verify and indicate this on the Service Calculations.
5. Sheet a0.1; Project Data: Per the IPC Section 410.2, drinking fountains are not required for an occupant load of 15 or fewer. Please verify and indicate this on the Service Calculations.
6. Sheet a0.1; Exiting Plan: Please revise the plan for the revised occupant load. The sum of the occupants using the two doors should equal the total occupant load.
7. Sheet a0.1; Project Data: The Fire Rated Construction indicates 0. The walls between this tenant space and the adjacent tenant spaces must follow the requirements of the IBC Section 708. Please list those requirements on this sheet.
8. Sheet a0.1; Exiting Plan: The maximum exit access travel distance should be listed on this sheet per the IBC Table 1017.2.
9. Sheet a0.2; Site Plan: Please review the site plan requirements per the IBC Section 107.2.6, and revise this drawing as required.
10. Sheet a5.0; Building Code Notes: Note 5 references the IBC Section 1008.1.8.7 for panic hardware. Please revise that reference.
11. Sheet a5.0; Building Code Notes: Note 16 references the IBC Section 106.1.1 for code information. Please revise that reference.
12. Sheet a9.0; Section 13: Per the IBC Section 708, this must be a one hour rated fire partition. Type X gypsum board will be required on both sides, or more than one layer will be required on just one side. Please provide a UL Listing Number for this wall on the Section 13.
13. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Constact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
10/21/2019 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: II Sons
Building plans (1st Review) 2500 E Grant Rd
T19CM07352 - C-2 Zoning - Related to DP18-0195

TRANSMITTAL DATE: October 21, 2019


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: COMMENT: Zoning has done a review of the building plans. In addition, while the building plans are consistent, as it relates to the zoning review purview zoning cannot approve the building plans until the Commercial Plans reviewer(s) have approved the building plans.

02. COMMENT: Zoning will review the building plans on the next submittal to assure consistency with the DP. Once the DP is approved by all reviewers and the building plans are approved by the Commercial Plans reviewers zoning can approve the building plans




If you have any questions about this transmittal, Contact Paul Camarena any time during the week at (520) 837-4082 or by email Paul.Camarena@Tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
10/31/2019 ROBERT SHERRY WATER REVIEW Completed
10/31/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide third-party listing and material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2018.
2. Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018.
3. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018.
11/01/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The 2018 IMC, IECC, IFGC, and IPC Codes as amended by the City of Tucson are the relevant codes for this project (not the UMC, the CMC, or the 2009 International codes).
2. Clarify the ventilation calculations; the demarcation of the various areas are not obvious (e.g. where is the separation between reception and barbershop, where is the office, and how is room 103 classified?). Use the net occupiable floor area (see definitions in Section 202, IMC 2018) to determine the number of occupants. Reference: Section 403.3.1.1.1.1, IMC 2018.
3. Revise the sequence of operation for exhaust fans EF-1 and EF-2 to operate concurrently with the roof top heat pump (i.e. on continuously during hours of operation). Reference: Sections 401.3 and 403.1, IMC 2018.
11/04/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The electrical notes call out the edition of the 2011 NEC. Please revise to the current 2017 NEC.
2. Provide a WP/ GFI protected receptacle on the roof within 25' of equipment for mechanical equipment maintenance. NEC 210.63.
Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal requirements. 2012 Tucson/Pima County Outdoor Lighting Code
11/05/2019 LOREN MAKUS ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/19/2019 SBORZAK1 REJECT SHELF Completed