The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T19CM07310
Parcel: 11012094F

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T19CM07310
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S3.01: Please provide a summary on this sheet (or an additional document) describing the scope of this revision.
2. Structural Calculations; Structural Design Criteria: This page indicates the structural calculations follow the 2012 IBC. Please revise that note to indicate the 2018 IBC, and verify the calculations are consistent with that Edition.
3. General: Please provide written responses to all review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/16/2020 ARUIZ1 APPROVAL SHELF Completed
11/16/2020 ARUIZ1 OUT TO CUSTOMER Completed