Permit Number: T19CM07194
Parcel: 136210180

Address:
7450 E STELLA RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM07194
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2019 MARTIN BROWN FIRE REVIEW Approved
10/09/2019 IMONSHI1 ZONING REVIEW Approved
10/16/2019 KROBLES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/16/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/16/2019 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Line Diagrams. Verify whether or not that the 1000-amp main service circuit breaker has integral ground fault detection equipment installed as required per NEC 230.95, 240.13. If yes, then provide compliance with NEC 705.32. This requirement (Ground Fault Protection) was added to the 1971 NEC to date.
2. Provide a grounding detail to show the method and materials/hardware used to ground the PV Panels.
3. Provide a detail showing how the inverters are mounted to the columns or elsewhere on the structure.
4. If not mounted in a readily accessible location, provide compliance with NEC 705.70.
5. Provide a permanent plaque at the electrical service equipment or point of interconnection that shows the location of Array #1 and #2 and associated disconnecting means or combiner panels. NEC 705.10.
Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal requirements.
11/01/2019 LOREN MAKUS ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/09/2020 PMARTIN1 OUT TO CUSTOMER Completed