Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM06991
Parcel: 12407038A

Address:
737 E 9TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T19CM06991
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2019 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T19CM06991
PLAN REVIEW COMMENTS
Plan review for the above referenced structure is completed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code, 2018 International Fire Code, 2017 National Electrical Code and Arizona Revised Statutes. All features were checked to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Make all corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

GENERAL NOTES:
" Provide compliance with the 2018 International Fire Code 1204.2.1.2 showing a 18" setback on both sides of the ridge when PV arrays are located on roof area where the slope is greater than 2:12. Update sheets PV-2 and PV-5.1.
NOTES / SPECIFICATIONS
1. Provide the exact wording and location for the "Photovoltaic System Disconnect" marking required by NEC 690.13 (B).
2. Provide the exact wording and location for the "Warning PV Power Source" required by NEC 690.31(G).
3. Provide the exact wording and location for the Power Source "Imp, Vmp, Vmax, Isc, Wmax" marking required by NEC 690.51.
4. Provide the exact wording and location for the "Rapid Shutdown Switch" marking required by NEC 690.56(C)
5. Show the back feed breaker at the opposite end on the panelboard from the main feeder location and label "Do Not Relocate", NEC 705.12 (B)(2)(3).

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
09/27/2019 PAUL CAMARENA ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/03/2019 QJONES1 APPROVAL SHELF Completed
10/03/2019 QJONES1 OUT TO CUSTOMER Completed
10/03/2019 QJONES1 REJECT SHELF Completed