10/04/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The exhaust fan schedule indicates that EF-1 will have a backdraft damper. Provide justification for the damper. Reference: Section 107.2.1, IBC 2018.
10/04/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The gas meter load chart shows "item # 30 range" with a 227 MBH load - where is it located? The load for #30 appears to be included in the total load shown on the gas diagram (C/P2). Reference: Section 1076.2.1, IBC 2018.
2. Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally (e.g. the grease interceptor). Reference: Section 905.4, IPC 2018.