Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM06981
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/04/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The exhaust fan schedule indicates that EF-1 will have a backdraft damper. Provide justification for the damper. Reference: Section 107.2.1, IBC 2018. |
| 10/04/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The gas meter load chart shows "item # 30 range" with a 227 MBH load - where is it located? The load for #30 appears to be included in the total load shown on the gas diagram (C/P2). Reference: Section 1076.2.1, IBC 2018. 2. Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally (e.g. the grease interceptor). Reference: Section 905.4, IPC 2018. |