Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM06934
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2019 | MASHFOR1 | FIRE | REVIEW | Approved | |
| 10/04/2019 | PAUL CAMARENA | ZONING | REVIEW | Approved | |
| 10/07/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 10/08/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The existing restrooms on the second floor are incorrect - they have been modified to be accessible. |
| 10/08/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 10/08/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/09/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G1.2; Code Review: The Code Review indicates the First Floor with 10,230 SF, the Second Floor with 7068 SF, and the Third Floor with 10,562 SF, while the Occupancy Schedule Table indicates 10,095 SF at the First Floor, 6892 SF at the Second Floor, and 9736 SF at the Third Floor. Please coordinate using the gross SF of each floor. 2. Sheet G1.2; Code Review: The Plumbing Fixtures indicate 185 total occupants for the three floors, while the Occupancy Schedule Table indicates 210 total occupants. Please coordinate. |
| 10/09/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide full compliance with the 2018 IECC for the lighting. 2. Provide a complete line diagram for the electrical service and downstream equipment. Include the new Panels and AIC ratings. 3. Provide total load calcs for the building. 4. Be more specific on the panel circuit directories for the device or lighting locations, room numbers or specific areas, corridors, etc. Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal requirements. |