Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T19CM06885
Parcel: 12616303A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM06885
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2020 MARTIN BROWN FIRE REVIEW Approved
01/27/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/29/2020 ROBERT SHERRY WATER REVIEW Completed
01/29/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Initial comment: Clarify the scope of work; building 9 is not included in the architect's scope of work and no "Building F" is shown on the site plan. Coordinate with the architect.]
01/29/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/05/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E5.2. Provide COMcheck for building #6 lighting.
2. Identify unit 'F' on the plans.
3. Ref; Plan Sheet A1.0 and E5.1, E5.2. It appears building #6 and #9 are reversed. Please clarify.
4. Identify units 6036 and 6037 on the electrical floorplans.
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/27/2020 KROBLES1 REJECT SHELF Completed