Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T19CM06832
Parcel: 130144510

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM06832
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2019 PAUL CAMARENA ZONING REVIEW Approved
09/20/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/20/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Plan Sheet E0.1 shows a new panel 'P2'. Provide a complete one line diagram. Include all panels and load calcs. Include total load in amps and KVA for the panel schedules.
Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.
09/20/2019 LOREN MAKUS ENGINEERING REVIEW Passed
09/20/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
09/20/2019 ROBERT SHERRY WATER REVIEW Completed
09/20/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/20/2019 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/23/2019 MARTIN BROWN FIRE REVIEW Approved