Permit Number: T19CM06828
Parcel: 124161510

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM06828
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2019 PAUL CAMARENA ZONING REVIEW Approved
09/19/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide cooling/heating load calculations.
2. Provide ventilation for the residential area
3. Dryer vents are 4" in diameter, not rectangular
09/19/2019 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide complete compliance with the 2018 IECC. Correlate with the luminaire schedule and lighting plans.
2. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code. www.tucsonaz.gov/pdsd.
3. Provide arc fault circuit breakers as required per NEC art 210.
4. The load calc in amps exceeds the rating of the panel for panel 'B'. See panel 'B' schedule.
5. Provide for tamper resistant receptacles. NEC 406.12.
Ref; 2017 NEC, 2018 IBC sec 107.2.1, 2018 IECC, 2012 Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.
09/19/2019 PCAMARE1 ENGINEERING REVIEW Passed
09/19/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide specifications for the plumbing fixtures.
2. Provide a riser diagram for the new waste & vent system.
3. Provide a list of the piping materials to be used.
09/19/2019 ROBERT SHERRY WATER REVIEW Reqs Change Verify the new water demand can be accommodated by the existing 5/8" water meter.
09/19/2019 MARTIN BROWN FIRE REVIEW Approved
09/27/2019 QJONES1 BUILDING-COMMERCIAL REVIEW Approved
09/27/2019 QJONES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/27/2019 QJONES1 APPROVAL SHELF Completed
09/27/2019 QJONES1 OUT TO CUSTOMER Completed
09/27/2019 QJONES1 REJECT SHELF Completed