Permit Number: T19CM06661
Parcel: 136153850

Review Status: Active

Review Details: RESUBMITTAL

Permit Number - T19CM06661
Review Name: RESUBMITTAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/27/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/27/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/17/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed The cooking appliances were installed under an earlier permit; no mechanical work under this activity. [Previous comment not addressed. Provide general room exhaust for any cooking appliance that is listed to UL-710B (e.g. Eikon convection oven) or a cooking appliance that does not require the installation of a Type II hood (e.g. Roller grill, microwave oven, etc.). The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2 and 507.3, IMC 2018.]
03/27/2020 IMONSHI1 ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/27/2020 ANY APPROVAL SHELF RECEIVED