Permit Review Detail
Review Status: Active
Review Details: RESUBMITTAL
Permit Number - T19CM06661
Review Name: RESUBMITTAL
Review Status: Active
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/27/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/27/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
02/27/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/17/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | The cooking appliances were installed under an earlier permit; no mechanical work under this activity. [Previous comment not addressed. Provide general room exhaust for any cooking appliance that is listed to UL-710B (e.g. Eikon convection oven) or a cooking appliance that does not require the installation of a Type II hood (e.g. Roller grill, microwave oven, etc.). The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2 and 507.3, IMC 2018.] |
03/27/2020 | IMONSHI1 | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/27/2020 | ANY | APPROVAL SHELF | RECEIVED |