Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - TI
Permit Number - T19CM06657
Review Name: COMMERCIAL - TI
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/09/2019 | MASHFOR1 | FIRE | REVIEW | Approved | |
| 10/10/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/10/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet 2944-FLC: Per the IBC Section 107.1, construction documents shall be prepared by a registered design professional. The documents shall include information as required the the IBC Section 107.2 where applicable. |
| 10/11/2019 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 10/11/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide complete electrical plans sealed by an Electrical Registrant registered in the state of Arizona. See the Commercial Plan Submittal Requirements (electrical) City of Tucson. www.tucsonaz.gov/pdsd. 2. Designate branch circuits and panels for all proposed electrical equipment, panel locations on the floor plans, complete panel schedules including load calcs. Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal requirements. |
| 10/11/2019 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: 1850 E Prince - Speedway Food Evolution 2019 T19CM06657 Building Plan (1st Review) TRANSMITTAL DATE: October 11, 2019 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. There should be two (2) separate pdf files for this submittal, one (1) for the application and one (1) for the plan. Once the applicable pdf files are provided Zoning can approved the plans. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 10/14/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood (e.g. Roller grill, microwave oven, etc.). The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.3, IMC 2018. |
| 10/14/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/14/2019 | ROBERT SHERRY | WATER | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/15/2019 | SBORZAK1 | OUT TO CUSTOMER | Completed |
| 09/13/2019 | ANY | REJECT SHELF | RECEIVED |