| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/03/2019 | PAUL CAMARENA | ZONING | REVIEW | Approved | |
| 10/10/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: Per the IBC Section 107.1, the construction documents must be prepared by a registered design professional of the jurisdiction in which the project is to be constructed. Please provide. |
| 10/15/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Designate a branch circuit and panel for the new power pole and deli case. 2. Show the location of the panel and provide a complete panel schedule include load calcs on the panel schedule. Provide the electrical plan sealed by an EE registered in the State of Arizona. Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/25/2019 | ANY | REJECT SHELF | RECEIVED |