Permit Number: T19CM06626
Parcel: 13219017F

Review Status: Active

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM06626
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2019 PAUL CAMARENA ZONING REVIEW Approved
10/10/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Per the IBC Section 107.1, the construction documents must be prepared by a registered design professional of the jurisdiction in which the project is to be constructed. Please provide.
10/15/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Designate a branch circuit and panel for the new power pole and deli case.
2. Show the location of the panel and provide a complete panel schedule include load calcs on the panel schedule. Provide the electrical plan sealed by an EE registered in the State of Arizona.
Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2019 ANY REJECT SHELF RECEIVED