Permit Number: T19CM06534
Parcel: 12714003E

Address:
6110 E 5TH ST #2

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM06534
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide the correct wiring methods on the electrical plans for the washer and the dryer. Correlate with the panel schedule, including load calcs.
Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements.
09/12/2019 MARTIN BROWN FIRE REVIEW Approved
09/17/2019 AMARTIN1 ZONING REVIEW Needs Review
09/17/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/17/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/17/2019 AMARTIN1 ENGINEERING REVIEW Needs Review
09/17/2019 AMARTIN1 BUILDING-COMMERCIAL REVIEW Needs Review
09/17/2019 ROBERT SHERRY WATER REVIEW Passed
09/17/2019 AMARTIN1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
09/18/2019 PCAMARE1 LANDFILL REVIEW Passed