Permit Number: T19CM06490
Parcel: 135101770

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T19CM06490
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2020 AMARTIN1 ENGINEERING REVIEW Needs Review
01/24/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
09/11/2019 PAUL CAMARENA ZONING REVIEW Needs Review ZONING REVIEW TRANSMITTAL


FROM: Paul Camarena
PROJECT:
T19CM06490, 2440 s Calle Cordova
New Front Garage addition
TRANSMITTAL: September 11, 2019
COMMENTS: The following comments are for the purpose of applying for a variance before the Board of Adjustment (UDC Section 3.10.1).

This site is located in the R-1 zone (UDC 4.7.9). Single-family residential is a permitted use in this zone (Table 4.8-2). See Use Specific Standards 4.9.7.B.6, .9 & .10.


The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall ((UDC 6.4.5.C.1.a). The required setback to the front street perimeter property line base on a wall height of 14' is 21ft. The proposed setback is 10'.


A variance is required.
09/11/2019 PCAMARE1 NPPO REVIEW Passed