Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T19CM06477
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/18/2019 | IMONSHI1 | ZONING | REVIEW | Reqs Change | Zoning cannot approve TI until building plans have been approved |
| 10/18/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/21/2019 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Please review section 5306 of the 2018 International Fire Code. Clearly indicate on plans how all components of the code are being satisfied, including fire ratings, ventilation, etc. for the med gas storage room. Lobby requires a second exit door that swings in the direction of egress travel. Choose one of the other doors (101A or 101B) to swing in the direction of egress travel. This will result in you having to modify exiting plan and exit sign placement. Please delineate changes in a response letter. |
| 10/22/2019 | QJONES1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/31/2019 | KROBLES1 | OUT TO CUSTOMER | Completed |