Permit Number: T19CM06477
Parcel: 133200160

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T19CM06477
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2019 IMONSHI1 ZONING REVIEW Reqs Change Zoning cannot approve TI until building plans have been approved
10/18/2019 ROBERT SHERRY WATER REVIEW Completed
10/21/2019 MARTIN BROWN FIRE REVIEW Reqs Change Please review section 5306 of the 2018 International Fire Code. Clearly indicate on plans how all components of the code are being satisfied, including fire ratings, ventilation, etc. for the med gas storage room.
Lobby requires a second exit door that swings in the direction of egress travel. Choose one of the other doors (101A or 101B) to swing in the direction of egress travel. This will result in you having to modify exiting plan and exit sign placement.
Please delineate changes in a response letter.
10/22/2019 QJONES1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/31/2019 KROBLES1 OUT TO CUSTOMER Completed