Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T19CM06409
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/10/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/16/2019 | IMONSHI1 | ZONING | REVIEW | Reqs Change | FROM: Iman Monshizadeh PDSD Zoning Review Section PROJECT: T19CM06409 - New Building - (Retail - Food Service) Building Plan Review (1st Review) Eegee's / Relate to DP19-0177 10158 E Old Vail Rd / C-1, I-2 Zoning TRANSMITTAL DATE: September 16th, 2019 DUE DATE: October 3rd, 2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning cannot approve until the Development package has been approved 2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. 3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning. 4. COMMENT: The building area square footage provided on the building plan (2,342 SF, sheet 2) does not match that of the Development package (2,445 SF, sheet 4) If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or by email Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov |
| 09/27/2019 | RMCCOY1 | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Commercial kithen hood ventilation ducts and exhaust equipment shall comply with the requirements of the 2018 IMC Section 506 . Commercial kitchen grease ducts shall be designed for the type of cooking appliance and hood served . Provide hood specifications and illustrate on plans. IMC Sec. 506. |
| 09/27/2019 | RMCCOY1 | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet P1 , the grease intercepter specified - Schier GB-75 has 4 inch FPT bulkhead connections and requires a 4 inch sewer . The plan illustrates a 3 inch sewer line to the grease intercepter . Please clarify and amend plans accordingly . IBC 107.2.1. |
| 09/27/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/02/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/02/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The electrical plans Registrant Seals are stamped "NOT FOR CONSTRUCTION". Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal requirements. |
| 10/16/2019 | LOREN MAKUS | ENGINEERING | REVIEW | Needs Review | 1. DP must be approved first. 2. Clearly show that primary roof drains will not be directed to sidewalks. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/31/2019 | AMARTIN1 | OUT TO CUSTOMER | Completed |