Permit Number: T19CM06382
Parcel: 11504490A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM06382
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2019 MALLORY RESS ZONING REVIEW Approved
09/03/2019 MRESS1 ENGINEERING REVIEW Passed
09/04/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/04/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide structural calculations and details showing how the fan coils are connected to the building structure.
09/04/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change Provide structural calculations for new fan coils.IBC107
Keynotes are not correct , please amend. IBC107.2.1
Respond in writting to plan review comments
09/04/2019 ROBERT SHERRY WATER REVIEW Completed
09/04/2019 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/05/2019 QJONES1 FIRE REVIEW Needs Review
09/05/2019 QJONES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/05/2019 QJONES1 APPROVAL SHELF Completed
09/05/2019 QJONES1 OUT TO CUSTOMER Completed
09/05/2019 QJONES1 REJECT SHELF Completed