Permit Number: T19CM06363
Parcel: 140020080

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM06363
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2019 PAUL CAMARENA ZONING REVIEW Approved
09/19/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/19/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/19/2019 ROBERT SHERRY WATER REVIEW Passed
09/25/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 04 (LR2363); Foundation Layout: The layout indicates Foundations A, B, and C, while the Foundation Types on Sheets 5, 6, and 7 indicate Foundation Types A, B, and D. Please verify.
2. Sheet 13 (LR2363); Section G-G: This section is not visible. Please revise.
3. Structural Calculations (Typical All): Is a calculation for the decking material (1" x 3/16" grating per General Note 2 on Sheet 12) provided in these calculations? Please verify.
4. General: Please provide the Special Inspectioin Certificate with Parts A and B completed. You may find this at www.tucsonaz.gov/PDSD.
5. General: Please provide written responses to all review comments.
09/25/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/27/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed
10/07/2019 JOHN VAN WINKLE ENGINEERING REVIEW Approved