Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM06363
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/18/2019 | PAUL CAMARENA | ZONING | REVIEW | Approved | |
| 09/19/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 09/19/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 09/19/2019 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 09/25/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet 04 (LR2363); Foundation Layout: The layout indicates Foundations A, B, and C, while the Foundation Types on Sheets 5, 6, and 7 indicate Foundation Types A, B, and D. Please verify. 2. Sheet 13 (LR2363); Section G-G: This section is not visible. Please revise. 3. Structural Calculations (Typical All): Is a calculation for the decking material (1" x 3/16" grating per General Note 2 on Sheet 12) provided in these calculations? Please verify. 4. General: Please provide the Special Inspectioin Certificate with Parts A and B completed. You may find this at www.tucsonaz.gov/PDSD. 5. General: Please provide written responses to all review comments. |
| 09/25/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/27/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 10/07/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved |