Permit Number: T19CM06331
Parcel: 14029043A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM06331
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The lighting area for Outdoor lighting is area E3, not E1. Please correct this and calculate lumens accordingly. Also the max allowed light source color temperature not to exceed 3500K sec 402.1.
2. Provide total load calcs for the service equipment.
3. Provide compliance with the 2018 IECC for lighting. Do not confuse this with the Outdoor Lighting Code.
Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.
10/25/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/28/2019 PMARTIN1 MECHANICAL-COMMERCIAL REVIEW Needs Review
10/28/2019 SARAH MEGGISON ZONING REVIEW Approved
10/28/2019 PMARTIN1 PLUMBING-COMMERCIAL REVIEW Needs Review
10/28/2019 PMARTIN1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/04/2019 SBORZAK1 REJECT SHELF Completed