Permit Number: T19CM06308
Parcel: 13216600B

Address:
4220 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM06308
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2019 MASHFOR1 FIRE REVIEW Approved
10/14/2019 SAMUEL ROGERS ZONING REVIEW Reqs Change FROM: Samuel Rogers
PDSD Zoning Review Section

PROJECT: T19CM06308
Solar Canopy (1st Review)
4300 S Park Ave.

TRANSMITTAL DATE: 10/14/2019

DUE DATE: 10/29/2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: 2-06.4.9.Q - Provide a height dimension from the mid-point of the top of the canopy to grade. Per UDC Article 6.6.3.C SPECIFICALLY WITHIN RESIDENTIAL ZONES - Accessory structures shall not exceed 12 feet in height, unless attached to a principal structure. The proposed structure exceeds the allowed 12 height and will require a Board of Adjustment for Variance.


02. COMMENT: Per Administrative Directive 1.07-7, all city owned properties requires an archaeology review.


03. COMMENT: This plan will not be approved until DP19-0209 is approved.




If you have any questions about this transmittal, Contact Samuel Rogers at (520) 837-6932 or email Samuel.Rogers@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
10/29/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan PV-4. Please correct detail 1 to indicate ONE LINE, not "THREE LINE".
2. Ref; Plan PV-4, PV-5. Please indicate the type of the Grounding Electrode utilized for the 75 KVA transformer. NEC 250.50.
Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal requirements.
11/04/2019 JGARCIA1 BUILDING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/07/2019 SBORZAK1 OUT TO CUSTOMER Completed