Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T19CM06195
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/23/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 04/27/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. The wall sections show R-19 batt insulation in the exterior walls but COMcheck calls out R-20 batt insulation. [Initial comment: Coordinate the wall insulation shown in the building section (A3.2) with the wall insulation shown in the wall sections on sheet D1 and the COMcheck envelope assemblies. Reference: Section 107.2.1, IBC 2018.] 2. Comment not resolved. Where is the long-vent dryer specified? Mechanical General Note #13 on sheet M1.1calls for a maximum equivalent dryer vent length of 35-feet. [Initial comment: The equivalent length of the dryer duct appears to be in excess of 35-feet. Provide the dryer manufacturer's installation instructions that support the proposed duct design. Reference: Section 504.8.4, IMC 2018.] |
| 05/01/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 05/13/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/14/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 05/28/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |